Reading of the power factor (PF) either through 

- Modbus protocol 5016, register 50012 (int16) or

- Modbus direct reading, register 160 (int16)


e.g. PF  -0.97 ... to ... 0.97


PF

leading / capacitive

- 0.97


1.00

lagging / inductive 

0.97


Factor x1000


-970


1000


970


Value at register 50012 / 160


FC36 hex


03E8 hex


03CA hex