Skip to main content

Suzlon MFR13 P/N 8441-1120 MFR1371M/DQ3RSU08UV replacement MFR300-71M/SU08 P/N 8444-1115 for windmill applicationSz - Knowledgebase / MFR300 - Power Generation

Suzlon MFR13 P/N 8441-1120 MFR1371M/DQ3RSU08UV replacement MFR300-71M/SU08 P/N 8444-1115 for windmill applicationSz

Authors list

SUZLON - P/N: 51025002 is Woodward’s P/N 8441-1120 was a customized multifunctional relay  called MFR1371M/DQRSU08UV mainly used on 2MW+ wind mills.  This MFR13 is connected via CAN bus to the upper level PLC.


This device has a special customized CAN protocol with option Su08.
P/N  8444-1115 MFR300-71M/SU08 comes with a compatible CAN protocol.


So MFR13 can get replaced by  this MFR300, thus you can make sure to maintain the upper PLC.


You can use the same configuration cable P/N 5417-557 DPC-1 or the latest P/N 5417-1251 DPC-USB can be used.


Mains differences :                                                                                                       

MFR13

MFR300

Dimensions:    96 x 72 x 130 mm

146x128x50 mm

690 VAC voltage sensing

690 VAC voltage sensing

../1A current sensing

../1A current sensing

Accuracy Class 1

Class 0.5 

MFR13M was with 8923-1023 Din rail brackets back panel mounted

back panel mounted

LeoPC configuration software

Toolkit software

2 line numeric dislpay

no display

1 x Discrete Input

no Discrete Input

8 x  Discrete Output  

5 x  Discrete Output  

only U, f , Df/Dt, monitoring

additional LVRT monitoring

CAN bus Su08

Can bus Su08


All MFR300 documentation can be downloaded here:

https://wss.woodward.com/manuals/PGC/MFR-x00_series/MFR-300

Toolkit Software:

https://wss.woodward.com/manuals/PGC/SW_Tools/ToolKit

Required configuration files:

https://wss.woodward.com/manuals/PGC/MFR-x00_series/MFR-300/02_Config_Files_