Reading of the power factor (PF) either through
- Modbus protocol 5016, register 50012 (int16) or
- Modbus direct reading, register 160 (int16)
e.g. PF -0.97 ... to ... 0.97
PF | leading / capacitive - 0.97 | 1.00 | lagging / inductive 0.97 |
Factor x1000 | -970 | 1000 | 970 |
Value at register 50012 / 160 | FC36 hex | 03E8 hex | 03CA hex |