People installing DTSC-200A , easYgen-400, -600, -800, - 1400, -1600 , - 1700 & -1800 controls in an 400, 440, 480 VAC voltage application are sometimes confused , if they are seeing this pic in instruction manual :
To be compliant to UL6200 Standard, we have to limit Line to Line voltages to max 300VAC.
The limitation factor is connectors' spacing from terminal to terminal of AC voltage measurement inputs.
If you built a control panel which is not according to UL6200 you can go up to 480VAC Line to Line as described in manuals
Technical Data: