easYgen-800/-1800 IDMT / Ground Fault formulas

作成者一覧

Formulas for Overcurrent / Ground Fault


  • IDMT Multiply of Overcurrent settings formula:
    T = t / ((IA/IT)-1)2

T:Overcurrent delay (seconds)

t:Timing multiplier ratio

IA:Current max. load current(L1/L2/L3)

IT:Overcurrent setting value


Example:


t = 36

IA = 550A

IT =500A


Conclusion: T = 3600 s



  • Delay Multiplier for Ground Fault formula:


ground current delay action calculation (0.1s)=delay multiplier*0.14/(((ground current/ground current threshold)0.02)-1)