メインコンテンツへスキップ

AC Voltage Sensing inputs DTSC-200A /easYgen-100/1000 controls - ナレッジベース / easYgen-800 - Power Generation

AC Voltage Sensing inputs DTSC-200A /easYgen-100/1000 controls

作成者一覧

People installing DTSC-200A  , easYgen-400, -600, -800, - 1400, -1600 , - 1700 & -1800  controls in an 400, 440, 480  VAC voltage application are sometimes confused , if they are seeing this pic in  instruction manual :

To be compliant  to  UL6200 standard, we have to limit Line to Line voltages  to max 300VAC.

Used voltage sensing connectors have UL up to 300V Line to Line (E-60425-19931013).

If you built a control panel which is not according to UL6200 you can go up to 480VAC Line to Line as described in manuals

Technical Data: