Do you want to build a
Ring Bus application with +32 generators and many more?
Here is how to connect +32 generators:
One GroupController GC3400XT is added to each powerplant and used as smart an IED (intelligent electronic device) load share gateway collecting all easYgen-3500XT within this group.
No need to connect current and voltage sensing but can be wired.
GC-3400XT's Group breaker is always seen as closed, as there is no physical group breaker
All GC3400XT communicating via Ethernet B & C redundant Ethernet to other GC-3400XTs.
Each GroupController communicate via CAN Ethernet A to each easYgen-3500XT within the group.
Each GroupController can placed within the group where it is convenient.
GroupControllers LDSS (Load dependent start & stop) functionality can be used to sequence individual gensets within each group.
Layer 1 n+1 easYgen-3500XT controls within one group are connected to above GC-3400XT in Layer 2.
Ring Bus Couplers & incoming Mains Feeders can be served by LS-6XT in Layer 3 as well:
Layer 1 n+1 easYgen-3500XT controls within one group are connected to above GC-3400XT in Layer 2
Documentation GroupController