DTSC-200
PN: 8440-1868-L
SW: 5418-6258-E
Message: the generation of a wset file breaks in Toolkit (the file settings were partially read and need to be resaved)
there will be no wset file generated
How to repair device?
- Execute factory default settings over Toolkit (ID 1704 = Yes, 1701 = Yes) in Codelevel 5
- Other possibility:
- in Toolkit, go to the page Parameter / Configure application / Display options
- Write the 4 Free message texts with ID 166622, 16623,16624 and 16625 to any value