Skip to main content

Are DSLC and DSLC-2 Loadshare Protocols compatible? - Knowledgebase / easYgen-3000XT - Power Generation

Are DSLC and DSLC-2 Loadshare Protocols compatible?

Authors list

No, old DSLC hat  LON load share Lines and DSLC-2 is using redundant E-Net load share  network.  

As well DSLC-2 Ethernet load share Protocol is not compatible with easYgen-3000XT Ethernet load share  network. (the LSG load share device doesn’t work either)

There is no LON / Ethernet Gateway available from Woodward.

The DSLC-2XT has the same incompatibility towards easYgen-3000XT.


DSLC-2 and DSLC-2XT are compatible of course!